TG61B
Section B: Basic Troubleshooting
Basic Troubleshooting
1. 
Check connections at B– cables, B+ cables,
B+ interconnect cable, B– interconnect cable,
and alternator-to-regulator harness. Repair or
replace any damaged component before trouble-
shooting.
2. 
Connections must be clean and tight.
3. 
If batteries are discharged, recharge or replace
batteries as necessary. Electrical system cannot
be properly tested unless batteries are charged
95% or higher. In addition, open circuit voltages
must be within ± 0.2 V.
4. 
Connect red lead of DMM to alternator anti-drive
end B+ terminal and black lead to alternator
anti-drive end B– terminal. Clamp inductive
ammeter on anti-drive end B+ cable.
5. 
Observe charge voltage at batteries with engine
running (nom. 27-28 V or 13.5-14.0 V).
SYMPTOM
ACTION
TABLE 1 – System Conditions
Check: loose drive belt; low battery
state of charge.
Check: current load on system is
greater than alternator can
produce.
Check: defective wiring or poor ground
path; low regulator setpoint.
Check: defective alternator or
regulator.
Check: wrong regulator.
Check: high regulator setpoint.
Check: defective regulator.
Check: alternator.
Check: broken drive belt.
Check: battery voltage at alternator
output terminal.
Check: defective alternator or regulator.
Go to Chart 2, page 6.
Low Voltage Output
High Voltage Output
No 28 V Output
Preliminary Check-out
Check symptoms in Table 1 and correct if necessary.
Tools and Equipment for Job
Digital Multimeter (DMM)
Ammeter (digital, inductive)
Jumper wires
Identification Record
List the following for proper troubleshooting:
Alternator model number _________________________
Regulator model number ________________________
Setpoint listed on regulator ______________________
CAUTION
No 14 V Output
If charge voltage is above
32 V for 28 V system or
16 V for 14 V system,
immediately shut down
system. Electrical system
damage may occur if charging
system is allowed to operate
at excessive voltage. Go to
Table 1 at left.
If voltage is at or below regulator setpoint, let
charging system operate for several minutes to
normalize operating temperature.
6. 
Charge voltage should increase and charge amps
should decrease. If charge voltage does not in-
crease within ten minutes, continue to next step.
7.  are considered fully charged if charge
voltage is at regulator setpoint and charge amps
remain at lowest value for 10 minutes.
8.  is not performing properly,
go to Chart 1, page 5.